Regenerative Resistors
For Teco:
- Most users will use the internal resistor; leave the jumper between PC-P1
- Persistent AL02 errors may require the addition of an external resistor to the servo drive
- For an external resistor, remove PC-P1 jumper and wire between P-PC
- Set Cn012 accordingly (Power setting for External Regeneration Resistor)
- See pg. 5-72 in Teco TSTA manual for calculation
For Yaskawa:
- If the drive has an internal resistor, there will be a jumper between B2-B3 terminals
- Some servopack models do not have an internal resistor so an external regenerative resistor is required
- For an external resistor, remove B2-B3 if present and wire between B1-B2
- Set Pn600 with the Regenerative Resistor Capacity
- A.320 alarm is because the resistor wattage has not been programmed or not set correctly
- See pg. 3-38 thru 3-40 for further details
Keywords:
regen resistor, Teco, Yaskawa, A.320, AL02